.TH mge-shut 8 "Thu Feb 26 2004" "" "Network UPS Tools (NUT)"
 
1
.TH mge\-shut 8 "Thu Feb 26 2004" "" "Network UPS Tools (NUT)" 
2
2
.SH NAME  
3
 
mge-shut \- Driver for MGE UPS serial SHUT Protocol UPS equipment
 
3
mge\(hyshut \- Driver for MGE UPS serial SHUT Protocol UPS equipment
4
4
.SH NOTE
5
 
This man page only documents the hardware-specific features of the
6
 
mge-shut driver.  For information about the core driver, see  
 
5
This man page only documents the hardware\(hyspecific features of the
 
6
mge\(hyshut driver.  For information about the core driver, see  
7
7
\fBnutupsdrv\fR(8).
8
8
 
9
9
.SH SUPPORTED HARDWARE
10
 
mge-shut support all recent MGE UPS models which use the SHUT (Serial HID
 
10
mge\(hyshut support all recent MGE UPS models which use the SHUT (Serial HID
11
11
UPS Transfer) protocol at 2400 bps. Supported models are:
12
12
 
13
13
    Pulsar Ellipse S,
 
14
        Pulsar Ellipse USBS
14
15
    Pulsar Ellipse Premium S,
 
16
        Pulsar Ellipse Premium USBS
15
17
    Pulsar EXtreme C,
16
18
    Pulsar Esprit,
17
 
    Pulsar / Comet EXtreme,
 
19
        Pulsar Evolution,
 
20
        NOVA AVR (Serial),
18
21
    Galaxy 3000 / PW (with RS232 HID COM ports card, ref 66066). 
19
22
 
20
 
Older models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U-Talk
21
 
protocol and should use the mge-utalk driver.
 
23
Older models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U\(hyTalk
 
24
protocol and should use the mge\(hyutalk driver.
22
25
 
23
26
.SH EXTRA ARGUMENTS
24
27
This driver supports the following optional settings in the 
32
35
 
33
36
.IP "offdelay=\fInum\fR"
34
37
Set the timer before the UPS is turned off after the kill power command is
35
 
sent (via the \fI-k\fR switch).
 
38
sent (via the \fI\-k\fR switch).
36
39
The default value is 20 (in seconds), and MUST BE LOWER than ondelay.
37
40
 
38
41
.IP "ondelay=\fInum\fR"
48
51
The default value is 3 (yes) because of some early Ellipse models which
49
52
need it.
50
53
 
 
54
.SH KNOWN ISSUES
 
55
.SS "Pulsar Ellipse S: Repetitive stale status \(hy Loss of communication"
 
56
 
 
57
Several users have reported "data stale" errors with Pulsar Ellipse 
 
58
equipment.  This lasts around 10 seconds and happens once every few hours.  
 
59
This is due to the fact that the SHUT protocol is verbose, and the driver 
 
60
sometimes does not handle all of it during the usual polling interval in 
 
61
upsd.  To solve this problem, change the value of MAXAGE to 25 in 
 
62
upsd.conf.  Also add "notification=3" in ups.conf (thanks to Julien 
 
63
Lesaint and Fabien).
 
64
 
51
65
 
52
66
.SH AUTHOR
53
67
Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>